id: 24645
Title: Planning of the experiment for the defining of the technical state of the transformer by using amplitude-frequency characteristic
Authors: Rubanenko O., Grishchuk M., Rubanenko O.
Keywords: diagnosis, faults, power transformer, frequency analysis, windings
Date of publication: 2020-04-21 09:32:28
Last changes: 2020-04-21 09:32:28
Year of publication: 2020
Summary: The article analyzes existing methods of diagnosing power transformers (PTs). The technique of experiment planning using D-optimal plans is investigated. According to the results of the study, a D-optimal plan of the frequency response measurements was created, which defines the algorithm of the studies. On the example of PT type TMG 1000/10 it is determined that 13 measurements are required to evaluate the condition of the PT during the interpretation of the results of the frequency response measurements. The method of determining the average frequency characteristic of PT is given. This amplitude-frequency characteristic can be used to check the PT status and to detect damage at an early stage of their development.
URI: http://socrates.vsau.edu.ua/repository/getfile.php/24645.pdf
Publication type: Статті Scopus
Publication: Przegląd elektrotechniczny. 2020. № 3. Р. 119-124.
In the collections :
Published by: Адміністратор
File : 24645.pdf Size : 391607 byte Format : Adobe PDF Access : For all
| |
|
|